FLANGED LINEAR VALVE

FLANGED LINEAR VALVE

GENERAL

These single-seated valves are used for modulating control of hot / chilled water or steam in heating, ventilating and air conditioning systems. Not suitable for use in open-circuit systems with oxygen enrichment. The valves can be operated by linear actuators ML6420/ML6425, ML7420/ML7425, ML6421/ML7421, or by pneumatic actuators MP953.

FEATURES

  • Iron body with flanged end connections
  • Low seat leakage rate
  • Metal-to-metal seating for long life span
  • Self-adjusting packing
  • Accurate positioning to ensure state-of-the-art temperature control
  • Easy mounting of direct-coupled electric and pneumatic actuators
  • Approved according to DI
SPECIFICATIONS
Action Stem down to close
Nominal pressure rating PN16
Flow characteristic Equal percentage, ngl = 3.4
Rangeability 50:1
Leakage rate 0.05% of kVS up to DN50
0.1% of kVS DN65 to DN150
Stroke 20 mm (DN15 to DN 80)
38 mm (DN100 to DN150)
Valve body
End connections
1/2″ bis 2″
Material Flanged per ISO 7005-2
Dimensions Cast iron (GG25)
Trim
Seat
Stainless steel, replaceable
Stem Stainless steel
Plug Stainless steel, skirt-guided
Packing Spring loaded PTFE cone rings
Medium temperature and pressure
20 mm
2…120 °C; max. 1600 kPa
120…150 °C; max. 1400 kPa
150…170 °C; max. 1370 kPa
38 mm 2…120 °C; max. 1600 kPa
120…150 °C; max. 1440 kPa
150…200 °C; max. 1280 kPa
Maximum temperature
differential in alternating
hot/cold water use
60 K

Download Resources

Title Download
Pressure Reducing Valves Download